Outdoor | SCM60ZS-W | |||
Power source (Outdoor) | 1 Phase 240V 50Hz | |||
*Operation data |
Nominal Capacity (Range) |
Cooling T1 |
kW |
6.0(1.7~7.5) |
Heating H1 | 6.8 (1.0~7.8) | |||
Power consumption |
Cooling T1 | 1.32 | ||
Heating H1 | 1.40 | |||
Running current |
Cooling T1 |
A |
5.6 | |
Heating H1 | 5.9 | |||
Inrush current, maximum current | 5, 15 | |||
EER | Cooling T1 | 4.55 | ||
COP | Heating H1 | 4.86 | ||
Sound power level (JIS C9612) |
Cooling T1 |
dB(A) |
62 | |
Heating H1 | 64 | |||
Sound pressure level (JIS C9612) |
Cooling T1 | 50 | ||
Heating H1 | 52 | |||
Silent mode |
Cooling T1 | 43 | ||
Heating H1 | 44 | |||
External dimensions (HxWxD) | mm | 640×850(+65)x290 | ||
Net weight |
kg |
48.5 | ||
Refrigerant (R32) |
Quantity | 1.8 | ||
Pre charged to pipe length | m | 40 | ||
Installation data |
Refrigerant piping |
Liquid line |
mm |
Ø6.35 x 3 |
Gas line | Ø9.52 x 3 | |||
Connection method | Flare connection | |||
Maximum pipe length to one indoor unit |
m |
25 | ||
Total pipe length to all indoor units | 40 | |||
Max vertical height diff. between O.U. and I.U. | 15 ( O.U. above I.U.) / 15 ( O.U. below I.U. ) | |||
Indoor Unit Combination |
SRK-ZSA-W |
kW |
2.0, 2.5, 3.5, 5.0 | |
SRK-ZSXA-W | 2.0, 2.5, 3.5, 5.0, 6.0 | |||
SRK-ZRA-W | ||||
SRF-ZS(X)-W | 2.5, 3.5, 5.0 | |||
SRR-ZS-W | 2.5, 3.5, 5.0, 6.0 | |||
FDTC-VH | 2.5, 3.5, 5.0, 6.0 | |||
FDUM-VH | 5.0 | |||
Indoor Unit Connection | 2 to 3 Units | |||
Indoor Connection Capacity | kW | 6.0 to 11.0 | ||
Outdoor air temperature (upper, lower limits) |
Cooling | °C | -15 to 46 | |
Heating | -15 to 24 |
Mitsubishi Heavy Industries 6kW Multi Head Outdoor Unit Only SCM60ZS-W
Next Day Delivery
If you checkout before 10am
Flexible Payment Options
Different payment options available
Guarantee Safe Checkout
Mitsubishi Heavy Industries SCM60ZS-W 6kW Multi Split System Outdoor Unit Only
For 2 – 3 Indoor Units
Maximum capacity of indoor units allowed: 11kW
Specifications
Warranty
All systems sold by Airconnex have a 5 year manufacturers warranty parts and labour.